電纜的燃燒測試 CSA Flame Test Ratings
蘇州工業(yè)園區(qū)力奧電子有限公司
收藏本文     查看收藏

 

國外電纜、電線的燃燒測試,分成各個級別;常見的網(wǎng)絡(luò)線CAT5,CAT6,CAT7等也基本遵循以下的燃燒測試;

http://www.highflexcables.com/dian-yuan-xian-ping-bi-xian-zi-liao.html

 

BLP BMR BM BLX
*Cable diameter must be less than 0.250″ **Cable diameter must be less than 0.375″

C(UL) Certifications;
UL/NEC-Approved cables may also be C(UL)/CEC-Approved as communications cables meeting the requirements of the Bi-National Standard CSA C22.2 No. 214/UL 444 and Section 60 of the Canadian Electrical Code, Part I (CEC). The C(UL) cable designation (and its meaning) would be one of the following:

1. CMP — Cable meeting CSA FT6 or NFPA 262 (UL 910);
2. CMR — Cable meeting UL 1666, CSA FT4
3. CMG — Cable meeting CSA FT4
4. CM — Cable meeting UL 1685 (UL 1581, Sec. 1160) Vertical-Tray, CSA FT1
5. CMX — Cable meeting UL 1581, Sec. 1080 (VW-1), CSA FT1
6. CMH — Cable meeting CSA FT1.

FLAME TESTS
FT1

FT1 Vertical Flame Test — per C.S.A. C22.2 No. 0.3-92 Para 4.11.1

A finished cable shall not propagate a flame or continue to burn for more than one (1) minute after five (5) fifteen (15) second applications of the test flame. There is an interval of fifteen (15) seconds between flame applications. The flame test shall be performed in accordance with Para 4.11.1 of Canadian Standards Association (CSA) Standard C22.2 No. 0.3. In addition, if more than 25% of the indicator flag is burned, the test cable fails. FT1 Cables can be used in Combustible buildings.

FT4

FT4 Vertical Flame Test — Cables in Cable Trays per C.S.A. C22.2 No. 0.3-92 Para 4.11.4

The FT4 Vertical Flame Test — Cables in Cable Trays is similar to the UL-1685 Vertical Tray Flame Test, but is more severe. The FT4 test has its burner mounted at 20° from the horizontal with the burner ports facing up. The UL-1685 Vertical Tray has its burner at 0° from the horizontal. The FT4 samples must be larger than 13mm (.512″) in diameter. If not, then the cable samples are grouped in units of at least three (3) to obtain a grouped overall diameter of 13mm. The UL-1581 Vertical Tray does not distinguish on cable size. The FT4 has a maximum char height of 1.5 m (59″) measured from the lower edge of the burner face. The UL-1685 has a flame height allowable up to approximately 78″ measured from the burner. FT4 Cables can be used in Non-Combustible buildings.

FT6

FT6 Horizontal Flame & Smoke Test — per C.S.A. C22.2 No. 0.3-92 Appendix B

Products passing the FT6 Horizontal Flame and Smoke Test are designated FT6 in the column where the trade number appears. This test is for cables which must pass a Horizontal Flame and Smoke Test in accordance with ANSI/NFPA Standard 262-1985 (UL-910). The maximum flame spread shall be 1.50 meters (4.92 ft.). The smoke density shall be 0.5 at peak optical density and 0.15 at maximum average optical density.

Combustible Construction

Combustible Construction; means that type of construction that does not meet the requirement for noncombustible construction. Combustible means that a material fails to meet the acceptance criteria of CAN/ULC S114, (Standard Method of test for determination of non-combustibility in Building Materials) (ref: NBC Part 1 Section 1.1.3.2).

Noncombustible Construction

Non-Combustible Construction; means that type of construction in which a degree of fire safety is

attained by the use of noncombustible materials for structural members and other building

assemblies. Non-Combustible means that a material meets the acceptance criteria of CAN/ULC S114, (Standard Method of test for determination of non-combustibility in Building Materials) (ref: NBC Part 1.1.3.2).

Cable Substitution Hierarchy as per C22.2 #214 — Communication Cables

The following cable substitution may be used:

A. Communication cables marked MPP, CMP, MPR, CMR, MPG, CMG, MP, CM, CMX, CMH, FT6, and FT4 have been found to meet the standard criteria for FT1.


B.
Communication cables marked MPP, CMP, MPR, CMR, MPG, CMG, and FT6 have been found to meet the standard criteria for FT4.


C.
Communication cables marked MPP and CMP have been found to meet the standard criteria for FT6.



 

狀 態(tài): 離線

公司簡介
產(chǎn)品目錄

公司名稱: 蘇州工業(yè)園區(qū)力奧電子有限公司
聯(lián) 系 人: 付小梁
電  話: 0189-13540512
傳  真: 8651267709070
地  址: 蘇州西中市閶門飯店3108
郵  編: 215003
主  頁:
 
該廠商相關(guān)技術(shù)文摘:
熱塑性彈性體具體介紹
戶外電纜的耐候性測試
電纜斷路點迅速查找排查
更多文摘...
立即發(fā)送詢問信息在線聯(lián)系該技術(shù)文摘廠商:
用戶名: 密碼: 免費注冊為中華工控網(wǎng)會員
請留下您的有效聯(lián)系方式,以方便我們及時與您聯(lián)絡(luò)

關(guān)于我們 | 聯(lián)系我們 | 廣告服務(wù) | 本站動態(tài) | 友情鏈接 | 法律聲明 | 不良信息舉報
工控網(wǎng)客服熱線:0755-86369299
版權(quán)所有 中華工控網(wǎng) Copyright©2022 Gkong.com, All Rights Reserved